Ductulator: Free Online Duct Size Calculator

Calculate the right duct size for any HVAC application. Enter CFM and velocity to get round duct diameter, equivalent rectangular sizes, and flex duct recommendations. No signup required.

Duct Size Calculator

Typical: 100-400 per room, 1200-2000 per system

Residential: 600-900 | Commercial: 1000-1800

Round Duct (Rigid)

inch diameter

Flex Duct (Recommended)

inch diameter

Equivalent Rectangular

Quick Reference: CFM by Room Type

How to Use This Ductulator

This ductulator calculates the correct duct diameter based on two inputs: the required airflow (CFM) and your target air velocity (FPM). The calculator outputs three results: the recommended round rigid duct diameter, the recommended flex duct diameter (sized larger to compensate for higher friction), and equivalent rectangular duct dimensions.

Step 1: Determine CFM

CFM (Cubic Feet per Minute) is the volume of air that needs to flow through the duct. For residential systems, each room has a CFM requirement based on its size, heat load, and the number of supply registers. The quick reference buttons above provide typical values. For precise CFM, use ACCA Manual J (heat load calculation) or consult your HVAC engineer.

Step 2: Choose Velocity

Air velocity determines how fast the air moves through the duct. Higher velocity allows smaller duct but increases noise and pressure drop. Standard ranges:

ApplicationMain Duct (FPM)Branch Duct (FPM)
Residential700-900400-600
Commercial (quiet)1,000-1,500600-1,000
Commercial (standard)1,500-2,0001,000-1,500
Industrial2,000-4,0001,500-3,000

Step 3: Read Results

The calculator snaps to standard duct sizes (4, 5, 6, 7, 8, 9, 10, 12, 14, 16, 18, 20, 24 inches). It also shows the exact calculated diameter so you can see how close the standard size is to the theoretical ideal. The flex duct recommendation is 15% larger than rigid to account for the corrugated inner surface that increases friction loss by 30-50%. See our flex duct sizes guide for detailed sizing tables by diameter.

Duct Sizing Principles

The fundamental equation behind every ductulator is: Area = CFM ÷ Velocity. For a round duct, Area = π × (D/2)², so D = √(4 × Area / π). This gives the minimum duct diameter to carry the required airflow at the target velocity.

In practice, you should always round up to the next standard size. An undersized duct increases velocity beyond the target, creating noise, excessive pressure drop, and reduced system performance. An oversized duct wastes material and space but does not hurt performance — when in doubt, size up.

Why Flex Duct Needs Larger Sizing

Flexible duct has a corrugated inner wall that creates significantly more friction than smooth rigid duct. At the same diameter and airflow, flex duct has 30-50% higher pressure drop. To deliver the same CFM with acceptable pressure drop, flex duct should be sized 1-2 inches larger than rigid duct.

This is why our calculator shows both rigid and flex recommendations. A system designed for 8-inch rigid duct should use 10-inch flex duct to maintain equivalent airflow performance. Additionally, flex duct must be pulled taut (fully extended) during installation — a compressed or sagging flex duct can lose 50% or more of its rated airflow capacity. See our installation guide for best practices.

Complete CFM Chart by Duct Size

For a comprehensive airflow capacity table covering every standard duct diameter from 4" to 24" at multiple velocities, see our dedicated flex duct CFM chart.

Frequently Asked Questions

What is a ductulator?
A ductulator is a duct sizing tool that calculates the correct duct diameter or rectangular dimensions based on airflow (CFM), air velocity (FPM), and friction rate. The name comes from the classic circular slide-rule ductulator card that HVAC engineers have used since the 1960s. Our online version provides the same calculations instantly with no manual lookup required.
How do I use a ductulator?
Enter the required CFM (airflow) for the room or zone and your target velocity (typically 600-900 FPM for residential, 1000-1800 FPM for commercial). The calculator outputs the recommended round duct diameter and equivalent rectangular sizes. For flex duct, add 1-2 inches to the calculated diameter to account for higher friction loss compared to smooth rigid duct.
What velocity should I use for duct sizing?
For residential HVAC: 600-900 FPM in main trunks, 400-600 FPM in branch runs. For commercial HVAC: 1000-1800 FPM in mains, 600-1200 FPM in branches. For industrial ventilation: up to 4000 FPM depending on the material being conveyed. Higher velocity means smaller duct but more noise and pressure drop.
What is equivalent duct diameter?
Equivalent duct diameter is the round duct size that has the same airflow capacity and friction loss as a given rectangular duct. For example, a 12×8 rectangular duct has an equivalent round diameter of approximately 10.4 inches. This conversion is essential when transitioning between round and rectangular sections in the same system.
Should I size flex duct differently than rigid duct?
Yes. Flex duct has 30-50% higher friction loss than smooth rigid duct at the same diameter due to its corrugated inner surface. When using flex duct, either increase the diameter by 1-2 inches compared to rigid duct calculations, or reduce the maximum run length. Our calculator accounts for this difference. See our flex duct sizes guide for detailed sizing tables.